Your browser is out of date.

You are currently using Internet Explorer 7/8/9, which is not supported by our site. For the best experience, please use one of the latest browsers.

40 to 720 Ton Accuchiller KSE Series Packaged Outdoor Chiller

Dual refrigeration circuit, 40 to 60 ton (141 to 211 kW)

Dual fluid & refrigeration circuit, 80 to 120 ton (281 to 422 kW)

KSE Series industrial outdoor air-cooled chillers feature a compact, all-in-one package designed to minimize installation cost, maximize usable space and lower electric bills. Designed for harsh outdoor environments KSE Series chillers require no options to operate within the standard -20°F to 125°F (-29°C to 52°C) ambient environment conditions. Standard process fluid temperatures of 20°F to 80°F (-7°C to 27°C) are ideal for industrial applications. The modular design allows up to 12 refrigeration circuits to be combined into a single system for up to 720 tons (2,532 kW) of cooling capacity.

Chillers are available with or without integrated pumping packages, including high and low pressure pumping with dedicated stand-by and built-in pressurized and non-pressured tanks.

KSE Series chillers come standard with Dynamic Lift technology to continuously calculate the lowest allowable refrigerant pressure for any combination of operating conditions to maximize chiller energy savings and to provide stable process fluid temperatures of +/- 2°F (1.1°C).

Learn More About Dynamic Lift Control Technology

Overview

  • Wide operating conditions
    • Ambient Environment: -20°F to 125°F (-29°C to 52°C)
    • Process Fluid Circuit: 20°F to 80°F (-7°C to 27°C)
  • Integral air-cooled rugged microchannel condenser for class-leading efficiency
  • Innovative PLC Control System with a large high-resolution color touch-screen operator interface and an extensive list of operational information including remote monitoring
  • Direct drive scroll compressors for low maintenance and energy efficiency
  • Compressor staging for capacity control with optional hot gas bypass for even greater unloading capabilities
  • Compressor anti-cycle and start-up timer
  • Lead/lag compressor staging to alternate primary compressor
  • Brazed plate evaporators maximize performance and increase resistance to costly freeze-up failures
  • Standard variable-speed drive fans reduce energy usage and provide optimum part-load performance for industry-leading IPLV, all while reducing noise levels for sound-sensitive environments  
  • C-UL 508A listed and labeled control panel
  • In-line evaporator strainers assure full evaporator performance
  • Single point connection for electric hookup at control cabinet
  • Electronic expansion valves
  • Liquid line solenoid valves to extend compressor life
  • Refrigerant sight glasses
  • Liquid line filter driers with removable cores
  • High and low refrigerant pressure switches
  • Alarm horn with silence button

  • 3-phase power monitoring and safety protection

  • EPA approved low GWP R-454B refrigerant or energy efficient R-410A refrigerant

Available Options

  • High and low pressure pumping with dedicated stand-by pump for quick and easy installation
  • Rotary non-fused disconnect switch
  • Hot-gas bypass minimum load capacity control
  • 5-year compressor parts warranty
  • Expert field start-up provided by qualified service personnel
  • CONNEX 4.0 for system-wide control

KSEA120T - 360 Image

PLC controls, monitors, and maintains stable and reliable operation of the chiller.

Learn More
KSE  Scroll Compressor Chillers PLC controls

Specification Tables

Dimensions and Weights ( Chiller w/High Pressure Pump)

Model KSEA040 KSEA050 KSEA060 KSEA080 KSEA100 KSEA120
Cooling Capacity¹ 40 ton chiller
141 kW
50 ton chiller
176 kW
60 ton chiller
211 kW
80 ton chiller
281 kW
100 ton chiller
352 kW
120 ton chiller
422 kW
Set Point Range  20 to 80°F
-7 to 27°C
20 to 80°F
-7 to 27°C
20 to 80°F
-7 to 27°C
20 to 80°F
-7 to 27°C
20 to 80°F
-7 to 27°C
20 to 80°F
-7 to 27°C
Compressor (qty) 2 2 2 4 4 4
Process In/Out(in) - Standard 3 3 4 4 4 4
Process In/Out(in) - High Flow 4 4 4 4 6 6
Dimensions and Weights ( Chiller Only)
Length 128 in
3,251 mm
173 in
4,394 mm
173 in
4,394 mm
128 in
3,251 mm
173 in
4,394 mm
173 in
4,394 mm
Width 47 in
1,194 mm
47 in
1,194 mm
47 in
1,194 mm
88 in
2,235 mm
88 in
2,235 mm
88 in
2,235 mm
Height 79 in
2,007 mm
79 in
2,007 mm
79 in
2,007 mm
79 in
2,007 mm
79 in
2,007 mm
79 in
2,007 mm
Ship Weight 2,876 lbs
1,305 kg
3,976 lbs
1,803 kg
3,976 lbs
1,803 kg
4,654 lbs
2,111 kg
5,954 lbs
2,701 kg
5,954
2,701 kg
Operating Weight  2,976 lbs
1,350 kg
4,251 lbs
1,928 kg
4,251 lbs
1,928 kg
4,754 lbs
2,156 kg
6,164 lbs
2,796 kg
6,229 lbs
2,825 kg
Flow, Pressure, Weights ( Chiller w/Standard Pressure Pump)
Process Pump/ Chiller Pump 7.5 hp
5.6 kW
7.5 hp
5.6 kW
10 hp
7.5 kW
15 hp
11.2 kW
15 hp
11.2 kW
15 hp
11.2 kW
Nominal Flow Rate  96 gpm
363 lpm
120 gpm
454 lpm
144 gpm
545 lpm
192 gpm
727 lpm
240 gpm
909 lpm
288 gpm
1,090 lpm
Nominal Discharge Pressure  41 psi
2.8 bar
39 psi
2.7 bar
50 psi
3.4 bar
54 psi
3.7 bar
50 psi
3.4 bar
62 psi
4.3 bar
Ship Weight  3,009 lbs
1,365 kg
4,109 lbs
1,864 kg
4,176 lbs
1,894 kg
4,858 lbs
2,204 kg
6,158 lbs
2,793 kg
6,223 lbs
2,823 kg
Operating Weight 3,109 lbs
1,410 kg
4,384 lbs
1,989 kg
4,451 lbs
2,019 kg
4,958 lbs
2,249 kg
6,368 lbs
2,888 kg
6,498 lbs
2,947 kg
Flow, Pressure, Weights ( Chiller w/Std Pressure Pump w/Dedicated Stby Pump)
Process Pump/ Chiller Pump  7.5 hp
5.6 kW
7.5 hp
5.6 kW
10 hp
7.5 kW
15 hp
11.2 kW
15 hp
11.2 kW
20 hp
14.9 kW
Nominal Flow Rate 96 gpm
363 lpm
120 gpm
454 lpm
144 gpm
545 lpm
192 gpm
727 lpm
240 gpm
909 lpm
288 gpm
1,090 lpm
Nominal Discharge Pressure 41 psi
2.8 bar
39 psi
2.7 bar
50 psi
3.4 bar
54 psi
3.7 bar
50 psi
3.4 bar
62 psi
4.3 bar
Ship Weight 3,142 lbs
1,425 kg
4,242 lbs
1,924 kg
4,376 lbs
1,985 kg
5,062 lbs
2,296 kg
6,362 lbs
2,886 kg
6,492 lbs
2,945 kg
Operating Weight 3,242 lbs
1,471 kg
4,517 lbs
2,049 kg
4,651 lbs
2,110 kg
5,162 lbs
2,341 kg
6,637 lbs
3,011 kg
6,767 lbs
3,070 kg
Flow, Pressure, Weights ( Chiller w/High Pressure Pump)
Process Pump/ Chiller Pump 15 hp
11.2 kW
15 hp
11.2 kW
15 hp
11.2 kW
25 hp
18.6 kW
25 hp
18.6 kW
25 hp
18.6 kW
Nominal Flow Rate  96 gpm
363 lpm
120 gpm
454 lpm
144 gpm
545 lpm
192 gpm
727 lpm
240 gpm
909 lpm
288 gpm
1,090 lpm
Nominal Discharge Pressure  86 psi
5.9 bar
82 psi
5.7 bar
80 psi
5.5 bar
90 psi
6.2 bar
82 psi
5.7 bar
76 psi
5.2 bar
Ship Weight  3,088 lbs
1,401 kg
4,188 lbs
1,900 kg
4,188 lbs
1,900 kg
4,977 lbs
2,258 kg
6,277 lbs
2,847 kg
6,277 lbs
2,847 kg
Operating Weight  3,188 lbs
1,446 kg
4,463 lbs
2,024 kg
4,463 lbs
2,024 kg
5,077 lbs
2,303 kg
6,487 lbs
2,942 kg
6,552 lbs
2,972 kg
Dimensions and Weights ( Chiller w/High Pressure Pump w/Dedicated Stby Pump)
Process Pump/ Chiller Pump 15 hp
11.2 kW
15 hp
11.2 kW
15 hp
11.2 kW
25 hp
18.6 kW
25 hp
18.6 kW
25 hp
18.6 kW
Nominal Flow Rate 96 gpm
363 lpm
120 gpm
454 lpm
144 gpm
545 lpm
192 gpm
727 lpm
240 gpm
909 lpm
288 gpm
1,090 lpm
Nominal Discharge Pressure  86 psi
5.9 bar
82 psi
5.7 bar
80 psi
5.5 bar
90 psi
6.2 bar
82 psi
5.7 bar
76 psi
5.2 bar
Ship Weight 3,300 lbs
1,497 kg
4,400 lbs
1,996 kg
4,400 lbs
1,996 kg
5,300 lbs
2,404 lbs
6,600 lbs
2,994 kg
6,600 lbs
2,994 kg
Operating Weight 3,400 lbs
1,542 kg
4,675 lbs
2,121 kg
4,675 lbs
2,121 kg
5,400 lbs
2,449 kg
6,810 lbs
3,089 kg
6,875 lbs
3,118 kg

¹Cooling tons based on 12,000 BTU/Hr/ton with 50°F (10°C) leaving coolant and 95°F (32°C) ambient air, R-410A or R-454B refrigerant.