TSE Scroll Compressor

Request a Quote

Single circuit (two compressors) 10 to 85 ton central chiller
Dual circuit (four compressors) 20 to 170 ton central chiller

The compact size of our newest central chiller minimizes floor space; while its modular design allows up to 12 refrigeration circuits to be combined into a single system for over 1,000 tons of cooling capacity. The chiller's innovative high flow design assures consistent process leaving water temperatures from 20°F to 80°F and as low as 5°F differential across the process.

TSE Series Chiller Features

      • Water-cooled and remote air-cooled condenser models available
      • Powerful PLC Control System with high-resolution color touch-screen operator interface with an extensive list of operational information including compressor run hours
      • Brazed plate evaporators maximize performance and increase resistance to costly freeze-up failures
      • Compressor staging for capacity control with optional hot gas bypass for even greater unloading capabilities
      • Scroll compressors last longer, increase efficiency and lower operating costs
      • C-UL 508A listed and labeled control panel
      • Compressor anti-cycle and start-up timer
      • Lead/lag switch to alternate primary compressor
      • In-line evaporator strainers assure full evaporator performance
      • Water-cooled chillers include condenser water regulating valves
      • Single point connection for electric hookup at control cabinet
      • Cleanable frame mounted water-cooled condensers with removable heads (water-cooled only)
      • Electronic expansion valves
      • Liquid line solenoid valves to extend compressor life
      • Refrigerant sight glasses
      • Liquid line filter driers with removable cores
      • High and low refrigerant pressure switches
      • Alarm horn with silence button
      • 3-phase power monitoring and safety protection
      • 410a refrigerant
      • Expert field start-up provided by qualified service personnel

Specification Tables

WATER COOLED CONDENSER SINGLE-CIRCUIT CHILLER GENERAL DATALearn More

Model TSEW 10STSEW 15STSEW 20STSEW 25STSEW 30STSEW 40STSEW 50STSEW 60STSEW 80S
General
Cooling Capacity(tons)¹ 10.9 16.1 22.2 27.3 32.6 42.2 53.3 68.4 86.2
Set Point Range (°F) 20 to 80 20 to 80 20 to 80 20 to 80 20 to 80 20 to 80 20 to 80 20 to 80 20 to 80
Process Fluid In/Out (in) 1.5 1.5 2 2 2.5 2.5 3 3 4
Condenser Water In/Out (in) 1.5 2 2 2.5 2.5 3 3 4 4
Refrigerant Charge (lbs of R410A) 10 30 30 35 40 50 70 80 100
Min Unloaded Capacity (ton) 5.5 8.1 11.1 13.7 16.2 21.0 25.9 33.9 42.6
with HGB Option (ton) 2.7 4.0 5.5 6.8 8.1 10.5 13.0 17.0 21.3
Dimensions, Weights, Amps (Chiller Only)
Length (in) 68 68 68 68 72 100 100 100 105
Width (in) 24 24 24 24 24 24 30 30 30
Height (in) 69 69 69 69 69 69 69 69 69
Shipping Weight (lbs) 950 1,050 1,150 1,150 1,350 1,800 1,850 2,250 2,550
Operating Weight (lbs) 965 1,070 1,180 1,183 1,387 1,860 1,920 2,336 2,640
MCA @ 460/3/60 (amps)² 22 34 42 53 62 71 86 124 165
Dimensions, Weights, Amps (Chiller w/ Standard Flow Reservoir Option, 10°F ΔT Process, 10°F ΔT Chiller)
Reservoir Capacity (gal) 275 275 275 275 275 275 275 450 450
Pump Models (Process/Chiller) 5D/1.5A 5D/1.5A 5D/1.5A 5D/1.5A 7.5D/2A 10D/2A 10D/3A 10D/3A 15D/3A
Process Connection Size (in) 1.5 1.5 2 2 2.5 2.5 3 3 4
Length (in) 84 84 84 96 96 96 96 108 108
Width (in) 72 72 76 76 76 92 92 95 100
Height (in) 75 75 75 75 75 75 75 75 75
Ship Weight (lbs) 2,650 2,750 2,850 2,950 3,250 3,800 4,000 4,700 5,500
Operating Weight (lbs) 4,950 5,050 5,150 5,250 5,550 6,100 6,300 8,450 9,250
MCA @ 460/3/60 (amps)² 32 43 50 62 75 86 104 141 188
Dimensions, Weights, Amps (Chiller w/ Standard Flow Reservoir Option, 5°F ΔT Process, 10°F ΔT Chiller)
Reservoir Capacity (gal) 400 400 400 400 400 400 400 650 650
Pump Models (Process/Chiller) 5D/1.5A 7.5D/1.5A 10D/1.5A 10D/1.5A 10D/2A 15D/2A 15D/3A 20D/3A 25D/3A
Process Connection Size (in) 2 2.5 2.5 3 3 4 4 4 6
Length (in) 84 84 84 96 96 96 96 108 108
Width (in) 72 72 76 76 76 92 92 95 100
Height (in) 76 76 76 76 76 76 76 76 76
Ship Weight (lbs) 2,850 2,950 3,100 3,150 3,450 4,000 4,250 4,950 5,750
Operating Weight (lbs) 6,200 6,300 6,450 6,500 6,800 7,350 7,600 10,400 11,200
MCA @ 460/3/60 (amps)² 32 46 57 68 78 91 109 153 201
 

¹Cooling capacity when cooling water with 50°F set point, 60°F return, 85°F condenser water, R-410A refrigerant.
²MCA is Minimum Circuit Ampacity (for wire sizing), complies with NEC, Section 430-24.

WATER COOLED CONDENSER DUAL-CIRCUIT CHILLER GENERAL DATALearn More

Model TSEW 20DTSEW 30DTSEW 40DTSEW 50DTSEW 60DTSEW 80DTSEW 100DTSEW 120DTSEW 160D
General
Cooling Capacity (tons)¹ 21.7 32.1 44.3 54.7 65.2 84.5 106.7 136.9 172.5
Set Point Range(°F) 20 to 80 20 to 80 20 to 80 20 to 80 20 to 80 20 to 80 20 to 80 20 to 80 20 to 80
Process Fluid In/Out (in) 2 2.5 2.5 3 3 4 4 4 6
Condenser Water In/Out (in)3 2 2.5 3 3 4 4 4 6 6
Refrig Charge/Cir (lbs of R410A) 10 30 30 35 40 50 70 80 100
Mini Unloaded Capacity (ton) 5.5 8.0 11.1 13.7 16.2 20.9 25.9 33.9 42.6
w/ HGBP Option (ton) 2.7 4.0 5.5 6.8 8.1 10.5 13.0 16.9 21.3
Dimensions, Weights, Amps (Chiller Only)
Length (in) 75 75 80 80 85 115 115 118 125
Width (in) 56 56 56 56 56 56 56 56 56
Height (in) 69 69 69 69 69 69 69 69 69
Ship Weight (lbs) 1,650 1,900 2,150 2,200 2,550 3,450 3,600 4,450 5,100
Operating Weights (lbs) 1,680 1,940 2,210 2,266 2,624 3,570 3,740 4,622 5,280
MCA @ 460/3/60 (amps)² 42 63 76 99 115 131 161 232 311
Dimensions, Weights, Amps (Chiller w/ Standard Flow Reservoir Option, 10°F ΔT Process, 10°F ΔT Chiller)
Reservoir Size (gal) 275 275 275 275 450 450 700 700 1,000
Pump Models (Process/Chiller) 5D/1.5A 7.5D/2A 10D/2A 10D/3A 10D/3A 15D/3A 15D/5A 20D/5A 25D/10E
Process Connection Size (in) 2 2.5 2.5 3 3 4 4 4 6
Length (in) 108 108 108 120 132 132 132 144 144
Width (in) 78 78 78 90 90 105³ 110³ 110³ 110³
Height (in) 75 75 75 75 75 75 75 75 90
Ship Weight (lbs) 3,650 4,100 4,450 4,650 5,200 6,550 7,200 8,300 10,150
Operating Weight (lbs) 5,950 6,400 6,750 6,950 8,950 10,300 13,050 14,150 18,500
MCA @ 460/3/60(amps)² 51 76 93 117 133 154 187 269 356
Dimensions, Weights, Amps (Chiller w/ Standard Flow Reservoir Option-1, 5°F ΔT Process, 10°F ΔT Chiller)
Reservoir Size (gal) 400 400 400 400 650 650 1,000 1,000 1,000
Pump Models (Process/Chiller) 10D/1.5A 10D/2A 15D/2A 15D/3A 20D/3A 25D/3A 30D/5A 40D/7.5F 40D/10E
Process Connection Size (in) 2.5 3 4 4 4 6 6 6 6
Length (in) 108 108 108 120 132 132 144 144 144
Width (in) 78 78 78 90 90 105³ 110³ 110³ 110³
Height (in) 76 76 76 76 76 90 90 90 90
Ship Weight (lbs) 5,950 6,400 6,750 6,950 8,950 10,300 13,050 14,150 18,500
Operating Weight (lbs) 7,200 7,650 8,000 8,200 10,900 12,250 16,250 17,250 19,500
MCA @ 460/3/60(amps)² 59 79 98 122 145 168 207 294 375
 

¹Cooling capacity when cooling water with 50°F set point, 60°F return, 85°F condenser water, R-410A refrigerant.
²MCA is Minimum Circuit Ampacity (for wire sizing), complies with NEC, Section 430-24.
³To keep the shipping dimensions within a 102" width for standard flatbed shipping, the condenser inlet mainfold is removed for shipping.

REMOTE AIR COOLED CONDENSER SINGLE-CIRCUIT CHILLER GENERAL DATALearn More

  TSER 10STSER 15STSER 20STSER 25STSER 30STSER 40STSER 50STSER 60STSER 80S
General
Cooling Capacity (tons)¹ 10.0 14.9 20.4 25.2 30.1 38.9 48.9 63.6 78.7
Set Point Range(°F) 20 to 80 20 to 80 20 to 80 20 to 80 20 to 80 20 to 80 20 to 80 20 to 80 20 to 80
Process Fluid In/Out (in) 1.5 1.5 2 2 2.5 2.5 3 3 4
Refrigerant Discharge Line (in) 7/8 1 1/8 1 1/8 1 3/8 1 3/8 1 5/8 1 5/8 1 5/8 2 1/8
Refrigerant Liquid Line (in) 5/8 7/8 7/8 1 1/8 1 1/8 1 1/8 1 1/8 1 3/8 1 5/8
Refrig Charge(lbs of R410A) Varies based on refrigerant system piping
Mini Unloaded Capacity (ton) 5.0 7.4 10.0 12.5 14.8 19.1 23.6 30.9 38.5
w/ HGBP Option (ton) 2.5 3.7 5.0 6.2 7.4 9.6 11.8 15.5 19.3
Dimensions, Weights, Amps (Chiller Only)
Length (in) 68 68 68 68 72 102 102 102 105
Width (in) 24 24 24 24 24 24 30 30 30
Height (in) 69 69 69 69 69 69 69 69 69
Ship Weight (lbs) 850 1,000 1,050 1,050 1,150 1,550 1,600 1,900 2,200
Operating Weight (lbs) 865 1,020 1,080 1,083 1,187 1,610 1,670 1,986 2,290
MCA @ 460/3/60 (amps)² 22 34 42 53 62 71 86 124 165
Dimensions, Weights, Amps (Chiller w/ Standard Flow Reservoir Option, 10°F ΔT Process, 10°F ΔT Chiller)
Reservoir Size (gal) 275 275 275 275 275 275 275 450 450
Pump Models (Process/Chiller) 5D/1.5A 5D/1.5A 5D/1.5A 5D/1.5A 7.5D/2A 10D/2A 10D/3A 10D/3A 15D/3A
Process Connection Size (in) 1.5 1.5 2 2 2.5 2.5 3 3 4
Length (in) 84 84 84 96 96 96 96 108 108
Width (in) 64 64 64 76 76 92 92 92 95
Height (in) 75 75 75 75 75 75 75 75 75
Ship Weight (lbs) 2,600 2,700 2,750 2,800 3,050 3,550 3,750 4,350 5,150
Operating Weight (lbs) 4,900 5,000 5,050 5,100 5,350 5,850 6,050 8,100 8,900
MCA @ 460/3/60(amps)² 32 43 50 62 75 86 104 141 188
Dimensions, Weighs, Amps (Chiller w/ Standard Flow Reservoir Option, 5°F ΔT Process, 10°F ΔT Chiller)
Reservoir Size (gal) 400 400 400 400 400 400 400 650 650
Pump Models (Process/Chiller) 5D/1.5A 7.5D/1.5A 10D/1.5A 10D/1.5A 10D/2A 15D/2A 15D/3A 20D/3A 25D/3A
Process Connection Size (in) 2 2.5 2.5 3 3 4 4 4 6
Length (in) 84 84 84 96 96 96 96 108 108
Width (in) 64 64 64 76 76 92 92 92 95
Height (in) 76 76 76 76 76 76 76 76 76
Ship Weight (lbs) 2,800 2,950 2,950 3,000 3,300 3,750 4,000 4,600 5,350
Operating Weight (lbs) 6,159 6,300 6,300 6,350 6,650 7,100 7,350 10,050 10,800
MCA @ 460/3/60(amps)² 32 46 57 68 78 91 109 153 201
 

¹Cooling capacity when cooling water with 50°F set point, 60°F return, 95°F condenser water, R-410A refrigerant.
²MCA is Minimum Circuit Ampacity (for wire sizing), complies with NEC, Section 430-24.

REMOTE AIR COOLED CONDENSER DUAL-CIRCUIT CHILLER GENERAL DATALearn More

  TSER 20DTSER 30DTSER 40DTSER 50DTSER 60DTSER 80DTSER 100DTSER 120DTSER 160D
General
Cooling Capacity (tons)¹ 20.4 29.9 40.7 50.5 60.2 77.8 97.7 127.2 157.5
Set Point Range(°F) 20 to 80 20 to 80 20 to 80 20 to 80 20 to 80 20 to 80 20 to 80 20 to 80 20 to 80
Process Fluid In/Out (in) 2 2.5 2.5 3 3 4 4 4 6
Refrigerant Discharge Line (in) 7/8 1 1/8 1 1/8 1 3/8 1 3/8 1 5/8 1 5/8 1 5/8 2 1/8
Refrigerant Liquid Line (in) 5/8 7/8 7/8 1 1/8 1 1/8 1 1/8 1 1/8 1 3/8 1 5/8
Refrig Charge/Cir (lbs of R410A) Varies based on refrigerant system piping
Mini Unloaded Capacity (ton) 5.0 7.3 10.0 12.5 14.7 19.1 23.6 30.9 38.5
w/ HGBP Option (ton) 2.5 3.7 5.0 6.2 7.4 9.6 11.8 15.5 19.3
Dimensions, Weights, Amps (Chiller Only)
Length (in) 75 75 80 80 85 105 105 110 125
Width (in) 48 49 48 48 48 48 48 48 52
Height (in) 69 69 69 69 69 69 69 69 69
Ship Weight (lbs) 1,550 1,800 1,850 1,900 2,150 2,900 3,000 3,650 4,250
Operating Weights (lbs) 1,580 1,840 1,910 1,966 2,224 3,020 3,140 3,822 4,430
MCA @ 460/3/60 (amps)² 42 63 76 99 115 131 161 232 311
Dimensions, Weighs, Amps (Chiller w/ Standard Flow Reservoir Option, 10°F ΔT Process, 10°F ΔT Chiller)
Reservoir Size (gal) 275 275 275 275 450 450 700 700 1,000
Pump Models (Process/Chiller) 5D/1.5A 7.5D/2A 10D/2A 10D/3A 10D/3A 15D/3A 15D/5A 20D/7.5F 25D/10E
Process Connection Size (in) 2 2.5 2.5 3 3 4 4 4 6
Length (in) 108 108 108 120 132 132 132 144 144
Width (in) 74 74 74 74 74 92 102 102 102
Height (in) 75 75 75 75 75 75 75 75 90
Ship Weight (lbs) 3,500 4,000 4,200 4,350 4,800 6,000 6,600 7,500 9,300
Operating Weight (lbs) 5,800 6,300 6,400 6,650 8,550 9,750 12,450 13,350 17,650
MCA @ 460/3/60(amps)² 51 76 93 117 133 154 187 269 356
Dimensions, Weights, Amps (Chiller with High Flow Reservoir Option 1, 5°F ∆T Process, 10°F ∆T Chiller)
Reservoir Size (gal) 400 400 400 400 650 650 1,000 1,000 1,000
Pump Models (Process/Chiller) 10D/1.5A 10D/2A 15D/2A 15D/3A 20D/3A 25D/3A 30D/5A 40D/7.5F 40D/10E
Process Connection Size (in) 2.5 3 4 4 4 6 6 6 6
Length (in) 108 108 108 120 132 132 132 144 144
Width (in) 74 74 74 74 74 92 102 102 102
Height (in) 76 76 76 76 76 76 76 76 90
Ship Weight (lbs) 3,850 4,200 4,400 4,550 5,050 6,250 7,300 8,100 10,300
Operating Weight (lbs) 7,200 7,550 7,750 7,900 10,500 11,700 15,650 16,450 18,650
MCA @ 460/3/60(amps)² 59 79 98 122 145 168 207 294 375
 

¹Cooling capacity when cooling water with 50°F set point, 60°F return, 95°F condenser water, R-410A refrigerant.
²MCA is Minimum Circuit Ampacity (for wire sizing), complies with NEC, Section 430-24


REMOTE AIR-COOLED SINGLE-CIRCUIT CONDENSER GENERAL DATALearn More

  KCM014KCL023KCL030KCL037KCL045KCL056KCL068KCL095KCL110
Chiller Model Used With¹ TSER10S TSER15S TSER20S TSER25S TSER30S TSER40S TSER50S TSER60S TSER80S
Dimensions
Length (in) 83 113 113 113 168 168 223 278 333
Width (in) 43 45 45 45 45 45 45 45 45
Height (in) 48 54 54 54 54 54 54 54 54
Weights
Ship Weight (lbs) 415 680 720 1,050 1,075 1,450 1,475 1,950 2,300
Operating Weight (lbs) Operating weight varies base on system refrigeration charge and operating conditions
General
Total Air Flow (cfm) 14,400 24,000 22,600 20,600 33,900 30,900 42,400 51,800 62,100
Sound Pressure Level (dBA)² 53 63 63 63 64 64 65 66 67
MCA @ 460/3/60 (amps)³ 2.6 7.0 7.0 7.0 10.1 10.1 16.0 16.0 21.0
Refrig Lines (in)
Inlet Per Circuit 1 3/8 2 1/8 2 1/8 2 1/8 2 5/8 2 5/8 2 5/8 3 1/8 3 1/8
Outlet Per Circuit 1 1/8 1 3/8 1 5/8 1 5/8 1 5/8 2 1/8 2 1/8 2 5/8 2 5/8

¹One condenser is required per chiller; dual-circuit chillers use one remote condenser that has two refrigeration circuits.
²Sound pressure level at 30 feet.
³MCA is Minimum Circuit Amps (for wire sizing) as provided by the remote condenser manufacturer.

REMOTE AIR-COOLED DUAL-CIRCUIT CONDENSER GENERAL DATALearn More

  KCM034KCL047KCL060KCL074KCL090KCL112KCL137KCL190KCL224
Chiller Model Used With¹ TSER20D TSER30D TSER40D TSER50D TSER60D TSER80D TSER100D TSER120D TSER160D
Dimensions
Length (in) 83 113 113 113 168 168 223 278 333
Width (in) 83 87 87 87 87 87 87 87 87
Height (in) 48 54 54 54 54 54 54 54 54
Weights
Ship Weight (lbs) 830 1,175 1,525 1,525 2,000 2,275 2,800 3,700 4,400
Operating Weight (lbs) Operating weight varies base on system refrigeration charge and operating conditions
General
Total Air Flow (cfm) 28,400 47,900 45,200 41,200 67,800 61,800 84,800 103,500 124,200
Sound Pressure Level (dBA)² 55 65 65 65 67 67 68 69 70
MCA @ 460/3/60 (amps)³ 4.9 16.0 16.0 16.0 21.0 21.0 24.8 36.0 46.0
Refrig Lines (in)
Inlet Per Circuit 1 5/8 2 1/8 2 1/8 2 1/8 2 1/8 2 5/8 2 5/8 3 1/8 3 1/8
Outlet Per Circuit 1 1/8 1 3/8 1 5/8 1 5/8 1 5/8 2 1/8 2 1/8 2 5/8 2 5/8

¹One condenser is required per chiller; dual-circuit chillers use one remote condenser that has two refrigeration circuits.
²Sound pressure level at 30 feet.
³MCA is Minimum Circuit Amps (for wire sizing) as provided by the remote condenser manufacturer.

Available Options

  • Rotary non-fused disconnect switch
  • Hot-gas bypass minimum load capacity control
  • ModBus RTU, BACnet, or LonWorks communications port
  • Integral reservoir and pumping system
  • 5-year compressor parts warranty
Resource Center
PLC Control System
Resource Image

The PLC Control System combines a controller, operation interface, I/O and networking capability into one seamless solution.

Learn More

Request a Quote

Submit a request for a FREE, no-obligation quote!

Ask A Question

Estimate Your Annual Energy Savings by Using a Thermal Care TC Series Central Chiller.
Save $10,000 - $30,000 Annually!
Calculate Savings